Installer essentials · October 2026

Installer essentials

ENTH-200 and ENTH-250. Key product and installation notes.

The two models

ENTH-200ENTH-250
TCL model codeKZd40-RS20WF-T3KZd40-RS25WF-T3
Stated capacity204 L250 L
Net size, W × D × H600 × 625 × 1,802 mm600 × 625 × 2,022 mm
Net / gross weight94 / 114 kg106 / 125 kg
Packed size, W × D × H690 × 690 × 1,960 mm690 × 690 × 2,180 mm
Water inlet, outlet, drainG 3/4"
Rated pressure0.85 MPa
Power supply220–240 V, 1 ph, 50 Hz
Power input850 W maximum heat pump; 2,450 W maximum with the 1,600 W element
Maximum water temperature70°C heat pump only; 75°C with element
Operating range−7 to +43°C heat pump; −25 to +43°C with element
RefrigerantR290, 150 g, GWP 3; not an F-gas
TankEnamelled steel; magnesium anode, electronic anode optional
Heat-up, 10 to 50°C, 15°C air6 h7.2 h
Sound power / pressure at 1 m53 dB(A) / 41 dB
ControlsWiFi, TCL Home app, over-the-air updates; SG-Ready and Modbus

Space and ducting

  • Room size, ventilation and service access must be checked for the exact installation. Do not treat the unit footprint as the required room size.Installer assessment required; TCL clarification outstanding
  • Clear space without ducts: at least 800 mm above the unit, and 2,000 mm and 800 mm to the walls at either side, as drawn in the manual.TCL installation and service manual V25.07.11.4, section 3
  • Ducting is optional: up to two ducts at the top, fresh air in and exhaust out, each up to 5 m, few elbows, insulated at least 15 mm. Rated static pressure 30 Pa, maximum 90 Pa.TCL installation and service manual V25.07.11.4, section 3.5
  • Provide condensate drainage. Safety-valve discharge must be designed separately to the applicable local rules, including visibility and safe termination; do not assume an ordinary floor drain is suitable. A dedicated fixed supply with an RCD and circuit breaker; no extension leads.TCL installation and service manual V25.07.11.4

Still being confirmed with TCL

  • UK energy label details

We publish each figure once TCL confirm it in writing. We do not estimate.

Regulations at a glance

  • Unvented hot water: follow the building regulations for the installation location. Use a competent unvented hot water installer. In England, a qualification demonstrates competence but does not itself remove notification: use an appropriate competent person scheme to self-certify, or notify building control before work starts. Scotland and Wales have their own applicable guidance.Approved Document G, 2024, paras 3.40 to 3.42
  • At least two independent safety devices in addition to any thermostat, for example a non self-resetting energy cut-out and a temperature and pressure relief valve.Approved Document G, 2024, paras 3.17 to 3.18
  • R290 is a natural refrigerant, not an F-gas. Follow the manufacturer's instructions, including the R290 guidance.TCL installation and service manual, on request
  • Can be specified as part of a Boiler Upgrade Scheme-funded system. Check current Ofgem scheme rules for each installation.Ofgem BUS installer guidance, version 5, paras 3.80 to 3.83

Cover

  • 24 months on every unit from enthalvia: whole appliance, parts and labour.
  • No registration and no annual service condition. Extendable up to six years with enthalvia Care. Ask for the full cover terms with your quotation and before you buy.
  • For units installed in England, Scotland and Wales.

If something goes wrong, send us

  1. The model, ENTH-200 or ENTH-250
  2. The TCL model code and serial number from the rating plate
  3. The installation date, and who fitted it
  4. What is happening, with a photo if you can

Contact

info@enthalvia.com
Technical questionSubject: Technical question
Installation manualSubject: Manual request
Stock and ordersSubject: Trade order
Fault or coverSubject: Cover question or fault